top of page
"ROC 2015 Reverse Osmosis Controller by The Water Solar Company - A cutting-edge water purification technology."

ROC 2015 Reverse Osmosis Controller (No EC Probe)

SKU: ROC-2015
R1,507.00Price

ROC 2015 Reverse Osmosis Controller

 

Introducing the ROC 2015 Reverse Osmosis Controller, an advanced RO program controller specifically designed for water treatment systems. This Microcomputer Controller boasts online monitoring capabilities and is perfect for industrial electrical applications.

 

The ROC-2015 is an essential component of any single-stage RO plant, providing a simple yet efficient means of controlling the entire water treatment process. From sand filter to multimedia filter, sediment filter, and high-pressure pump, this controller displays the real-time running status of the RO machine.

 

Equipped with a flashing light alarm system, the ROC-2015 promptly notifies users of any malfunction. Resetting and restarting the controller is effortless, ensuring continuous operation without delay.

 

Ideal for small-scale first-class anti-osmosis water preparation systems, the ROC 2015 is focused on automatic operation management. By incorporating a few peripheral electric elements, it enables seamless automation of anti-osmosis devices.

 

Featuring five digital input (DI) ports and four output control ports, this compact and cost-effective ROC controller is the perfect solution for your water treatment needs.

 

Controller Functions

  • FS:High-pressure and low-pressure flushing selection
  • HP:Access terminal for overpressure detection of Booster (high pressure) pump (normally closed, disconnecting in case of overpressure, and short out COM at top right corner when not using)
  • NW:Detection on low level of original water tank or low pressure of pipeline (use liquid level switch or pressure switch and installation of sampling point)
  • LP:Access terminal of switch for detecting security filter pressure at back of low-pressure pump(Contact normally open, and closed when up to the pressure as required)
  • LC: Input terminal of switch for detecting level of pure water tank (normally closed, disconnecting in case of the water full and closed meeting low liquid level)
  • EC:Whether the control system operates for access terminal for external control(control by remote and panel switch)
  • COM: Common port for upper acquisition terminal
  • AC220V: Firewire end for 220V power supply (220V AC powers on); Zero line for power grid
  • COM: Common point for control relay
  • IV: Output contact for controlling on and off of water feeding solenoid valve (normally open and passive)
  • FV: Control contact for on and off of RO flushing solenoid valve (normally open and passive)
  • LM: Contact for controlling start/stop of booster pump(normally open and passive)
  • HM: Contact for controlling start/stop of low-pressure water pump (normally open and passive)

All the above control ports are terminals of dry contact of relay(without power distribution), sharing COM common terminal.

bottom of page